Documents/Reports
Minimum Oil Circuit Breaker : Bhel Make HLD Type
Weekly Maintenance :
| 20 D-01 W |
Checking of Oil Level in Each Pole:
|
|||
| 20 D-02 W |
Checking of Visible Oil Leakage :
|
|||
| 20 D-03 W |
Checking of Silica Gel Breather for Color Change :
|
|||
Quarterly Maintenance:
| 20 D-04 Q |
Checking of Heater Function :
|
|||
| 20 D-05 Q |
Visual Inspection of Breaker and Operating Mechanism :
|
|||
| 20 D-06 Q |
Checking of Breaker Operation and Removal of Coatings Developed on Current Carrying Parts of the Breaker, Remains for Long Time in the Closed Position :
|
|||
| 20 D-07 Q |
Checking of Oil Leaking From Oil Dash Pot in Operating Mechanism :
|
|||
| 20 D-08 Q |
Checking of Gas Vent :
|
|||
| 20 D-09 Q |
Lubrication :
|
|||
| 20 D-10 Q |
Cleaning of The Breaker :
|
|||
| 20 D-11 Q |
Checking of Dielectric Strength of Oil :
|
|||
| NOTE : The circuit breaker should be overhauled regularly, the first time after one year operation and there after every third year unless operational experience motivates other periods. | ||||
Tripping Based Maintenance :
|
||||
| 20 D-12 T |
Checking of Dielectric Strength of Oil :
|
|||
| 20 D-13 T |
Checking of Plug Contacts Burning :
|
|||
| Dimensions at a1 and a2 in mm. new tip a1 – a2 = 50 mm. used tip a1 – a2 = 56 mm. |
||||
| 20 D-14 T |
Checking of Extinguishing Chamber :
|
|||
Yearly Maintenance :
| 20 D-15 Y | Do as described in sub para | 20 D- 12 T | 2008 T | P 37 |
| 20 D-16 Y | -do- | 20 D- 13 T | P 43 | |
| 20 D-17 Y | -do- | 20 D- 14 T | P 43 | |
| 20 D-18 Y |
Cleaning and Lubrication :
|
|||
| 20 D-19 Y |
Checking/Tightening of All Electrical Terminal Connections :-
|
|||
| 20 D-20 Y |
Checking/Tightening of All Electrical Terminal Connections :- -
|
|||
| 20 D-21 Y |
Checking Of Auxiliary Switch :
|
|||
| 20 D-22 Y |
Checking Of Limit Switches And Friction Clutch :
|
|||
| 20 D-23 Y |
Checking Of Spring Charging Motor :
|
|||
| 20 D-24 Y |
Checking Of Tripping Of Trip Coil At 50% Dc Rated Voltage :
|
|||
| 20 D-25 Y |
Checking Of Contact Resistance :
|
|||
Maintenance After Every Third Year :
| 20 D-26 TR |
Overhaul the circuit breaker by carrying out the maintenance works listed under sub paras of yearly maintenance. Testing of the breaker for the following functions be also done every third year : |
|||
| 20 D-27 TR |
Leakage In Shaft Oil Seal : :
|
|||
| 20 D-28 TR |
Overhauling Of Extinguishing Chamber :
|
|||
| 20 D-29 TR |
Speed Measurement :
|
|||
| 20 D-30 TR |
Resistance Measurement Of Contacts In Current Path :
|
|||
| 20 D-31 TR |
Measurement Of Closing Time & Opening Time Of The Breakers :
|
|||
Maintenance After 15 To 20 Years Of Service :
|
||||
Lubrications :
|
||||