Documents/Reports
Air Blast Circuit Breaker (Type DCVF) HBB Make
The breaker is designed on the unit construction principle comprising the following main blocks :-
- Arc Extinction Units.
- Control Units
- Supporting insulators.
- Air receivers.
- Apparatus cubicle.
A complete 220 kV 132 kV breakers consist of three identical poles with control cabinet containing the controls.
Constructional Features:
Basically each pole of a breaker comprises a compressed air receiver, which are mounted on the vertical supporting hollow insulators which carry the arc extinction chambers. The receiver also carries the control unit and the main valves which are placed just below the hollow in insulators columns. These insulators columns also act as pressure pipes for transmitting the compressed air from the reservoir to the arc extinction chambers through main valves. Each pressure pipe is provided with ventilating cartridge which keeps the hollow insulator continuously ventilated with dry expanded air preventing condensation inside the insulator when the breaker is closed.
The control block mounted on the receiver is the nerve centre of the breaker and contains all the elements for the centre of the breaker such as control solenoids, control pistons and valves for closing and opening of the breaker. Each control block is also provided with a heater and an auxiliary switch.
The arc interrupter units, which are housed in the arc chamber insulators are connected electrically in series, the number of interrupters depending upon the voltage rating and the breaking capacity.
Each breaker is provided with a control apparatus cubicle which houses the following :-
- A double control valve operated locally by push buttons for opening and closing of the breaker, with a device to block, in the event of low pressure.
- A pressure gauge.
- A set of pressure switches to block closing, opening and re-closing respectively in the event of low pressure.
- A pneumatic supervision device with ‘ON’ & “OFF” indicator and auxiliary switch.
- Heater elements to keep the air in the cabinet dry and warm.
- Series terminals for wiring connectors to breaker poles and control room.
Operation:
The control of the main breaker is extremely simple. If there is no compressed air in the chamber, the contacts are kept closed by strong springs. When the compressed air flows into the chamber, the contact open. after extinction of the arc the exhaust of the chamber is closed so that the open contacts remain under compressed air. Thus the entire control operation consists in supplying compressed air through the insulator columns to the arc extinction chambers and venting these columns. No mechanical coupling whatsoever is provided between the base of the breaker unit and the arc extinction chambers.
when an order to open or to close the breaker is given, this passes from the control cabinet to electro pneumatic valves incorporated in the control block mounted on their receiver. These control valves in turn actuate all the main valves of the breaker. These main valves are fitted directly on their tank at the foot of the corresponding columns.
Pneumatic Supervision :
In case of a command to close, if anyone pole does not close, and other tow poles close then immediately closed poles will open again and similarly in case of a command to open, if one of the poles does not open, it receives a direct command to open after a set time lag. In both the above cases, an alarm contact is energized which is used to sound a bell or a hooter.
Yearly Maintenance :
| 20 A-01 Y | Cleaning : |
|
|
| 20 A-02 Y | Air Leakage : |
|
|
| 20 A-03Y | Earthing : |
|
|
| 20 A-04Y | Lubrication : |
|
Proper lubrication (as detailed in manual) be done at following points.
Note : Graphite oil and DC 55 M Silicon Grease are only to be used. |
|
| 20 A-05 Y | Foundation : |
|
|
| 20 A-06 Y | Heaters : |
|
|
| 20 A-07 Y | Wiring Connections : |
|
|
| 20 A-08 Y | Jumpers and Clamps : |
|
|
| 20 A-09Y | Tripping of Breker : |
|
|
| 20 A-10 Y | Tripping of Breaker At 50% D.C. Voltage : |
|
|
| 20 A-11 Y | Contact Resistance : |
|
|
| 20 A-12 Y | |
|
Tripping Based Maintenance :
| 20 A-13 T |
|
| 20 A-14 T |
|
Maintenance After Every 5 Years :
To be carried out regardless of number of operations executed by the breaker.
| 20 A-15 F | Hollow Insulator Columns : |
|
Examine inside of all hollow insulators including those of resistor contacts. Clean inside with acetone and mulmul cloth and ensure that no remains of cloth is left out before reassembly. Please follow instruction manual. |
|
| 20 A-16 F | Ventilation Cartridge : |
|
Remove ventilation cartridge (1005) and carry out test according to instruction in appendix 'C' of maintenance manual. Do not interchange the V-cartridge valve. |
|
| 20 A-17 F | Back Signaling Device : |
|
Dismantle back signaling device, clean it carefully with petrol, before assembly apply thin film of graphite oil to piston (4203) and (4214) and to the internal wall of the cylinder. |
|
| 20 A-18 F | Main Valve : |
| Dismantle back signaling device, clean it carefully with petrol, before assembly apply thin film of graphite oil to piston (4203) and (4214) and to the internal wall of the cylinder. | |
| 20 A-19 F | Air Receivers : |
|
Inspect (Clean and dry) the inner side of air receiver (proceed as per 20 A-15 F) |
|
| 20 A-20 F | Control Block : |
|
|
| 20 A-21 F | Apparatus Cubicle : |
|
|
| 20 A-22 F | Filters : |
|
|
| 20 A-23 F | General : |
|
|
| 20 A-24 F | Important : |
|
|
| 20 A-25 F | Refilling and Checking of ABCB : |
|